Electrical Thumb Rules-(Part 7, 8 & 9)

Overhead Conductor /Cable Size:

Voltage
Overhead Conductor
Cable Size
33 KV
ACSR-Panther/Wolf/Dog , AAAC
150,185,300,400,240 mm2 Cable
11 KV
ACSR-Dog/Recon/Rabbit , AAAC
120, 150,185,300 mm2 Cable
LT
ACSR-Dog/Recon/Rabbit , AAC,AAAC
95,120, 150,185,300 mm2 Cable

 Transmission / Distribution Line:

Span
Height of Tower
400KV=400 Meter
400KV=30Meter (Base 8.8 Meter)
220KV=350 Meter
220KV=23Meter (Base 5.2 Meter)
132KV=335 Meter
220KV Double Circuit=28 Meter
66KV=210 Meter
66KV=13Meter
Conductor Ampere
Voltage wise Conductor
Dog=300Amp
400KV=Moose ACSR=500MVA Load
Panther=514Amp
220KV=Zebra ACSR=200MVA Load
Zebra=720Amp
132KV=Panther ACSR=75MVA Load
Rabbit=208Amp
66KV=Dog ACSR=50MVA Load
Moose=218Amp

 Type of Tower:

Type
Used
Angle/Deviation
A
Suspension Tower
Up to 2°
B
Small Angle Tower
2° to 15°
C
Medium Angle Tower
15° to 30°
D
Large Angle / Dead End Tower
30° to 60° & Dead End

 Tower Swing Angle Clearance (Metal Part to Live Part):

Swing Angle
Live Part to Metal Part Clearance (mm)
66KV
132KV
220KV
400KV
915mm
1530mm
2130mm
3050mm
15°
915mm
1530mm
2130mm
22°
3050mm
30°
760mm
1370mm
1830mm
44°
1860mm
44°
610mm
1220mm
1675mm

 Cable Coding (IS 1554) A2XFY / FRLS / FRPVC / FRLA / PILC)

A
Aluminium
2X
XLPE
F
Flat Armoured
W
Wire Armoured
Y
Outer PVC Insulation Sheath
W
Steel Round Wire
WW
Steel double round wire Armoured
YY
Steel double Strip Armoured
FR
Fire Retardation
LS
Low Smoke
LA
Low Acid Gas Emission
WA
Non Magnetic round wire Armoured
FA
Non Magnetic Flat wire Armoured
FF
Double Steel Round Wire Armoured

 Corona Ring Size:

Voltage
Size
<170 KV
160mm Ring put at HV end
>170 KV
350mm Ring put at HV end
>275 KV
450mm Ring put at HV end & 350 mm Ring put at Earth end

 Load as per Sq.Ft:

Type of Load
Load/Sq.Ft
Diversity Factor
Industrial
1000 Watt/Sq.Ft
0.5
Commercial
30 Watt/Sq.Ft
0.8
Domestic
15 Watt/Sq.Ft
0.4
Lighting
15 Watt/Sq.Ft
0.8

  Size of Ventilation Shaft:

Height of Building in meter
Size of ventilation shaft in sq meter
Minimum size of shaft in meter
9.0
1.5
1.0
12.5
3.0
1.2
15 and above
4.0
1.5

Electrical Thumb Rules-(Part-8)

OCTOBER 1, 2013 10 COMMENTS

Accuracy Class of Metering CT:

Metering Class CT
Class
Applications
0.1 To 0.2
Precision measurements
0.5
High grade kilowatt hour meters for commercial grade kilowatt hour meters
3
General industrial measurements
3 OR 5
Approximate measurements

 Accuracy Class Letter of CT:

Metering Class CT
Accuracy Class
Applications
B
Metering Purpose
Protection Class CT
C
CT has low leakage flux.
T
 CT can have significant leakage flux.
H
 CT accuracy is applicable within the entire range of secondary currents from 5 to 20 times the nominal CT rating. (Typically wound CTs.)
L
 CT accuracy applies at the maximum rated secondary burden at 20 time rated only. The ratio accuracy can be up to four times greater than the listed value, depending on connected burden and fault current. (Typically window, busing, or bar-type CTs.)

 Accuracy Class of Protection CT:

Class
Applications
10P5
Instantaneous over current relays & trip coils: 2.5VA
10P10
Thermal inverse time relays: 7.5VA
10P10
Low consumption Relay: 2.5VA
10P10/5
Inverse definite min. time relays (IDMT) over current
10P10
IDMT Earth fault relays with approximate time grading:15VA
5P10
IDMT Earth fault relays with phase fault stability or accurate time grading: 15VA

Electrical Thumbs Rules (Part-9)

MARCH 15, 2014 8 COMMENTS

Load in Multi-storied Building (Madhyanchal Vidyut Vitran Nigam)

Type of Load
Calculation
Diversity
Domestic  (Without Common Area)
50 watt / sq. meters
0.5
Commercial  (Without Common Area)
150 watt / sq. meters
0.75
Lift, Water Pump, Streetlight ,Campus Lighting ,Common Facilities,
Actual load shall be calculated
0.75

Load in Multi-storied Building (Noida Power Company Limited)

Type of Load
Calculation
Diversity
Domestic (Constructed area)
15 watt / sq. Foot
0.4
Commercial(Constructed area)
30 watt / sq. Foot
0.8
Industrial (Constructed area)
100 watt/ 1 sq. Foot
0.5
Lift, Water Pump, Streetlight ,Campus Lighting ,Common Facilities,
0.5Kw / Flat

Voltage Drop: 2% Voltage drop from Transformer to Consumer end.
T&D Losses: 2% T&D Losses from Transformer to Consumer end.

Approximate % Cost or Sq.Foot Cost

Project Item
% of Total Project Cost
Rs per Sq.Foot
Articheture (Consultancy)
0.7%
13.1 Rs / Sq.Foot
Structural (Consultancy)
1.2%
21.8 Rs / Sq.Foot
Service Design (Consultancy)
0.4%
7.2 Rs / Sq.Foot
Fire Fighting Work
1.3%
23 Rs / Sq.Foot
Electrical Work (Internal)
4.1%
76 Rs / Sq.Foot
Lift Work
4.4%
82 Rs / Sq.Foot

Street Light Costing (CPWD-2012)

Fluorescent Lamp
95 Rs/Sq.Meter
With HPMV Lamp
130 Rs/Sq.Meter
With HPSV Lamp
165 Rs/Sq.Meter
Electrical Sinage
85 Rs/Sq.Meter

Other Electrical Cost

Area Required for Solar Light
10 Watt/Sq.Foot
Solar Power Installation
1.5 Lacs Rs/1Kw
HVAC Cost
18 Watt/Sq.Foot

Distribution Losses (Gujarat Electricity Board)

Voltage (Point of Injection)
At 11 KV
Point of Energy Delivered
11KV / 22KV / 33KV
10%
1082%
400 Volt
16.77%

Rate Analysis (CPWD-2012)

Description
Amount
Sub Station Equipment
7000 Rs/ KVA
D.G Set with installation
1000 Rs / KVA
UPS with 30min Breakup
20000 Rs / KVA add 8000 Rs / KVA additional each 30 min
Solar Power Generation
1.25 Lacs / KW
Solar Water System (200Liter/Day)
46000 Rs
Solar Water System (300Liter/Day)
64000 Rs
Solar Water System (1000Liter/Day)
210000 Rs
Central AC Plant
75000 RS / Ton
VRF / VRV System
55000 Rs / HP
Air condition System
11000 Rs / Ton
CCTV System
300 Rs / Sq Meter
Access Control system
200 Rs / Sq Meter
Hydropenumatic Water system
2000 Rs / LPM
Building Management System
300 Rs /  Sq Meter add 100 Rs / Sq Meter additional area beyond 10000 Sq Meter

Rate Analysis (Rs per Sq. Meter) (CPWD-2012)

Work
Office/College/Hospital
School
Hostel
Residence
Fire Fighting (with Wet Riser)
500
500
500
500
Fire Fighting (with Sprinkler)
750
750
750
750
Fire Alarm (Manually)
300
Fire Alarm (Automatic)
500
500
500
500
Pressurized  Mechanical Ventilation
650
650
650
650

Rate Analysis (% of Total Project Cost) (CPWD-2012)

Work
Office/College/Hospital
School
Hostel
Residence
Internal Water Supply & Sanitary
4%
10%
5%
12%
Internal Electrical Installation
12.5%
12.5%
12.5%
12.5%

Lift Speed (Indian Army Manual)

No of Floor
Lift Speed
4 to 5
0.5 to 0.7 meter/Sec
6 to 12
0.75 to 1.5 meter/Sec
3 to 20
1.5 to 2.5 meter/Sec
Above 20
 Above 2.5 meter/Sec

Lift  Details (CPWD-2012)

Type of Lift 
Persons
Weight
Speed  M/Sec
Travel
Price
Add Rs /Floor
Passenger Lift 
8 Person
544 Kg
1.0
G+4
18 Lacs
1.25 Lacs
Passenger Lift 
13 Person
844 Kg
1.5
G+4
22 Lacs
1.25 Lacs
Passenger Lift 
16 Person
1088 Kg
1.0
G+4
28 Lacs
1.50 Lacs
Passenger Lift 
20 Person
1360 Kg
1.5
G+4
30 Lacs
1.50 Lacs


MCB Class according to Appliances

Appliance
Capacity / watt
MCB Rating
MCB Class
Air Conditioner
1.0 Tone
10A
C Class
1.5 Tone
16A
C Class
2.0 Tone
20A
C Class
Freeze
165 Liter
3 A
C Class
350 Liter
4 A
C Class
Oven /Grill
4500 Watt
32 A
B Class
1750 Watt
10 A
B Class
Oven / Hotplate
750 Watt
6 A
B Class
2000 Watt
10 A
B Class
Room Heater
1000 Watt
6 A
B Class
2000 Watt
10 A
B Class
Washing Machine
300 Watt
2 A
C Class
1300 Watt
8 A
C Class
Water Heater
1000 Watt
6 A
B Class
2000 Watt
10 A
B Class
3000 Watt
16 A
B Class
6000 Watt
32 A
B Class
Iron
750 Watt
6 A
B Class
1250 Watt
8 A
B Class
Toaster
1200 Watt
8 A
B Class
1500 Watt
10 A
B Class

1 comment:

  1. Hoff & Mazor delivers military-grade secure iPhone app development solutions that protect against modern cyber threats! Your team's expertise in end-to-end encryption and biometric security shines in projects like the healthcare app that passed rigorous HIPAA audits. For sensitive applications, your secure iPhone app development solutions provide unmatched data protection.