Sub Station Capacity & Short Circuit Current Capacity:

As per GERC
Voltage
Sub Station Capacity
Short Circuit Current
400 KV
Up to 1000 MVA
40 KA  (1 to 3 Sec)
220 KV
Up to 320 MVA
40 KA  (1 to 3 Sec)
132 KV
Up to 150 MVA
32 KA  (1 to 3 Sec)
66 KV
Up to 80 MVA
25 KA  (1 to 3 Sec)
33 KV
1.5 MVA to 5 MVA
35 KA (Urban) (1 to 3 Sec)
11 KV
150 KVA to 1.5 MVA
25 KA (Rural) (1 to 3 Sec)
415 V
6  KVA to 150 KVA
10 KA  (1 to 3 Sec)
220 V
Up to 6 KVA
6 KA  (1 to 3 Sec)

 Sub Station Capacity & Short Circuit Current Capacity:

As per Central Electricity Authority
Voltage
Sub Station Capacity
Short Circuit Current
765 KV
4500 MVA
31.5 KA for 1 Sec
400 KV
1500 MVA
31.5 KA for 1 Sec
220 KV
500 MVA
40 KA for 1 Sec
110/132 KV
150 MVA
40 KA or 50 KA for 1 Sec
66 KV
75 MVA
40 KA or 50 KA for 1 Sec

 Minimum Ground Clearance and Fault Clearing Time:

Voltage
Min. Ground Clearance
Fault Clear Time
400 KV
8.8 Meter
100 mille second
220 KV
8.0 Meter
120 mille second
132 KV
6.1 Meter
160 mille second
66 KV
5.1 Meter
300 mille second
33 KV
3.7 Meter

11 KV
2.7 Meter

 Bus bar Ampere Rating:

For Phase Bus bar
Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase Bus bar
Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral Bus bar
Same as Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at least half of Phase Bus bar.

 Bus bar Spacing:

Between Phase and Earth
26mm (Min)
Between Phase and Phase
32mm (Min)
Bus bar Support between Two Insulator
250mm.

 Sound Level of Diesel Generator (ANSI 89.2&NEMA 51.20):

KVA
Max. Sound Level
<9 KVA
40 DB
10 KVA to 50 KVA
45 DB
51 KVA to 150 KVA
50 DB
151 KVA to 300 KVA
55 DB
301 KVA to 500 KVA
60 DB

IR Value of Transformer:

IR Value of Transformer
Voltage
30°C
40°C
50°C
>66KV
600MΩ
300MΩ
150MΩ
22KV to 33KV
500MΩ
250MΩ
125MΩ
6.6KV to 11KV
400MΩ
200MΩ
100MΩ
<6.6KV
200MΩ
100MΩ
50MΩ
415V
100MΩ
50MΩ
20MΩ

Standard Size of MCB/MCCB/ELCB/RCCB/SFU/Fuse:


MCB
Up to 63 Amp (80Amp and 100 Amp a    per Request)
MCCB
Up to 1600 Amp (2000 Amp as per Request)
ACB
Above 1000 Amp
MCB Rating
6A,10A,16A,20A,32A,40A,50A,63A
MCCB Rating
0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A (Domestic Max 6A)
RCCB/ELCB
6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
Sen. of ELCB
30ma (Domestic),100ma (Industrial),300ma
DPIC (Double Pole Iron Clad) main switch
5A,15A,30 A for 250V
TPIC (Triple Pole Iron Clad) main switch
30A, 60A, 100A, 200 A For 500 V
DPMCB
5A, 10A, 16A, 32A and 63 A for 250V
TPMCCB
100A,200A, 300Aand 500 A For 660 V
TPN main switch
30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB
16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A, 300A, 500 A For 660 V
TPN Fuse Unit (Rewirable)
16A,32A,63A,100A,200A
Change over switch (Off Load)
32A,63A,100A,200A,300A,400A,630A,800A
SFU (Switch Fuse Unit)
32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
HRC Fuse TPN (Bakelite)
125A,160A,200A,250A,400A.630A
HRC Fuse DPN (Bakelite)
16A,32A,63A
MCB/MCCB/ELCB Termination Wire / Cable
Up to 20A MCB
Max. 25 Sq.mm
20A to 63A MCB
Max. 35 Sq.mm
MCCB
Max. 25 Sq.mm
6A to 45A ELCB
16 Sq.mm
24A to 63A ELCB
35 Sq.mm
80A to 100A ELCB
50 Sq.mm