Sub Station Capacity & Short
Circuit Current Capacity:
As per GERC
|
||
Voltage
|
Sub Station Capacity
|
Short Circuit Current
|
400 KV
|
Up to 1000 MVA
|
40 KA (1 to 3 Sec)
|
220 KV
|
Up to 320 MVA
|
40 KA (1 to 3 Sec)
|
132 KV
|
Up to 150 MVA
|
32 KA (1 to 3 Sec)
|
66 KV
|
Up to 80 MVA
|
25 KA (1 to 3 Sec)
|
33 KV
|
1.5 MVA to 5 MVA
|
35 KA (Urban) (1 to 3 Sec)
|
11 KV
|
150 KVA to 1.5 MVA
|
25 KA (Rural) (1 to 3 Sec)
|
415 V
|
6 KVA to 150 KVA
|
10 KA (1 to 3 Sec)
|
220 V
|
Up to 6 KVA
|
6 KA (1 to 3 Sec)
|
Sub
Station Capacity & Short Circuit Current Capacity:
As per Central Electricity Authority
|
||
Voltage
|
Sub Station Capacity
|
Short Circuit Current
|
765 KV
|
4500 MVA
|
31.5 KA for 1 Sec
|
400 KV
|
1500 MVA
|
31.5 KA for 1 Sec
|
220 KV
|
500 MVA
|
40 KA for 1 Sec
|
110/132 KV
|
150 MVA
|
40 KA or 50 KA for 1 Sec
|
66 KV
|
75 MVA
|
40 KA or 50 KA for 1 Sec
|
Minimum Ground Clearance and
Fault Clearing Time:
Voltage
|
Min.
Ground Clearance
|
Fault
Clear Time
|
400 KV
|
8.8 Meter
|
100 mille
second
|
220 KV
|
8.0 Meter
|
120 mille
second
|
132 KV
|
6.1 Meter
|
160 mille
second
|
66 KV
|
5.1 Meter
|
300 mille
second
|
33 KV
|
3.7 Meter
|
|
11 KV
|
2.7 Meter
|
|
Bus bar
Ampere Rating:
For Phase
Bus bar
|
Aluminium
130 Amp / Sq.cm or
800Amp / Sq.inch.
|
For Phase
Bus bar
|
Copper 160
Amp / Sq.cm or
1000Amp / Sq.inch
|
For
Neutral Bus bar
|
Same as
Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at least half of
Phase Bus bar.
|
Bus bar Spacing:
Between
Phase and Earth
|
26mm (Min)
|
Between
Phase and Phase
|
32mm (Min)
|
Bus bar
Support between Two Insulator
|
250mm.
|
Sound Level of Diesel
Generator (ANSI 89.2&NEMA 51.20):
KVA
|
Max. Sound Level
|
<9 KVA
|
40 DB
|
10 KVA to 50 KVA
|
45 DB
|
51 KVA to 150 KVA
|
50 DB
|
151 KVA to 300 KVA
|
55 DB
|
301 KVA to 500 KVA
|
60 DB
|
IR Value of Transformer:
IR Value of Transformer
|
|||
Voltage
|
30°C
|
40°C
|
50°C
|
>66KV
|
600MΩ
|
300MΩ
|
150MΩ
|
22KV to 33KV
|
500MΩ
|
250MΩ
|
125MΩ
|
6.6KV to 11KV
|
400MΩ
|
200MΩ
|
100MΩ
|
<6.6KV
|
200MΩ
|
100MΩ
|
50MΩ
|
415V
|
100MΩ
|
50MΩ
|
20MΩ
|
Standard Size of
MCB/MCCB/ELCB/RCCB/SFU/Fuse:
MCB
|
Up to 63
Amp (80Amp and 100 Amp a per Request)
|
MCCB
|
Up to 1600
Amp (2000 Amp as per Request)
|
ACB
|
Above 1000
Amp
|
MCB Rating
|
6A,10A,16A,20A,32A,40A,50A,63A
|
MCCB
Rating
|
0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
(Domestic Max 6A)
|
RCCB/ELCB
|
6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
|
Sen. of
ELCB
|
30ma
(Domestic),100ma (Industrial),300ma
|
DPIC
(Double Pole Iron Clad) main switch
|
5A,15A,30
A for 250V
|
TPIC
(Triple Pole Iron Clad) main switch
|
30A, 60A,
100A, 200 A For 500 V
|
DPMCB
|
5A, 10A,
16A, 32A and 63 A for 250V
|
TPMCCB
|
100A,200A,
300Aand 500 A For 660 V
|
TPN main
switch
|
30A, 60A,
100A, 200A, 300 A For 500 V
|
TPNMCB
|
16A,
32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A, 300A, 500 A For 660 V
|
TPN Fuse
Unit (Rewirable)
|
16A,32A,63A,100A,200A
|
Change
over switch (Off Load)
|
32A,63A,100A,200A,300A,400A,630A,800A
|
SFU
(Switch Fuse Unit)
|
32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
|
HRC Fuse
TPN (Bakelite)
|
125A,160A,200A,250A,400A.630A
|
HRC Fuse
DPN (Bakelite)
|
16A,32A,63A
|
MCB/MCCB/ELCB Termination Wire / Cable
|
|
Up to 20A MCB
|
Max. 25 Sq.mm
|
20A to 63A MCB
|
Max. 35 Sq.mm
|
MCCB
|
Max. 25 Sq.mm
|
6A to 45A ELCB
|
16 Sq.mm
|
24A to 63A ELCB
|
35 Sq.mm
|
80A to 100A ELCB
|
50 Sq.mm
|