Electrical
Thumb Rules-(Part 1).
§ Cable Capacity:
§ For Cu Wire Current Capacity (Up to
30 Sq.mm) = 6X Size of Wire in Sq.mm
§ Ex. For 2.5 Sq.mm=6×2.5=15 Amp,
For 1 Sq.mm=6×1=6 Amp, For 1.5 Sq.mm=6×1.5=9 Amp
§ For Cable Current Capacity = 4X Size
of Cable in Sq.mm ,Ex. For 2.5 Sq.mm=4×2.5=9 Amp.
§ Nomenclature for cable Rating = Uo/U
§ where Uo=Phase-Ground Voltage,
U=Phase-Phase Voltage, Um=Highest Permissible Voltage
§ Current Capacity of Equipments:
§ 1 Phase Motor draws Current=7Amp per HP.
§ 3 Phase Motor draws Current=1.25Amp per
HP.
§ Full Load Current of 3 Phase Motor=HPx1.5
§ Full Load Current of 1 Phase Motor=HPx6
§ No Load Current of 3 Phase Motor =30% of
FLC
§ KW Rating of Motor=HPx0.75
§ Full Load Current of equipment =1.39xKVA
(for 3 Phase 415Volt)
§ Full Load Current of equipment =1.74xKw
(for 3 Phase 415Volt)
§ Earthing Resistance:
§ Earthing Resistance for Single Pit=5Ω ,Earthing Grid=0.5Ω
§ As per NEC 1985 Earthing Resistance should
be <5Ω.
§ Voltage between Neutral and
Earth <=2 Volts
§ Resistance between Neutral and
Earth <=1Ω
§ Creepage Distance=18 to 22mm/KV (Moderate
Polluted Air) or
§ Creepage Distance=25 to 33mm/KV (Highly
Polluted Air)
§ Minimum Bending Radius:
§ Minimum Bending Radius for LT Power
Cable=12xDia of Cable.
§ Minimum Bending Radius for HT Power
Cable=20xDia of Cable.
§ Minimum Bending Radius for Control
Cable=10xDia of Cable.
§ Insulation Resistance:
§ Insulation Resistance Value for Rotating
Machine= (KV+1) MΩ.
§ Insulation Resistance Value for Motor (IS
732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
§ Insulation Resistance Value for Equipment
(<1KV) = Minimum 1 MΩ.
§ Insulation Resistance Value for Equipment
(>1KV) = KV 1 MΩ per 1KV.
§ Insulation Resistance Value for Panel
= 2 x KV rating of the panel.
§ Min Insulation Resistance Value (Domestic)
= 50 MΩ / No of Points. (All Electrical Points with Electrical fitting
& Plugs). Should be less than 0.5 MΩ
§ Min Insulation Resistance Value
(Commercial) = 100 MΩ / No of Points. (All Electrical Points without
fitting & Plugs).Should be less than 0.5 MΩ.
§ Test Voltage (A.C) for Meggering
= (2X Name Plate Voltage) +1000
§ Test Voltage (D.C) for Meggering = (2X
Name Plate Voltage).
§ Submersible Pump Take 0.4 KWH of extra
Energy at 1 meter drop of Water.
§ Lighting Arrestor:
§ Arrestor have Two Rating=
§ (1) MCOV=Max. Continuous Line to Ground
Operating Voltage.
§ (2) Duty Cycle Voltage. (Duty Cycle
Voltage>MCOV).
§ Transformer:
§ Current Rating of Transformer=KVAx1.4
§ Short Circuit Current of T.C
/Generator= Current Rating / % Impedance
§ No Load Current of Transformer=<2% of
Transformer Rated current
§ Capacitor Current (Ic)=KVAR / 1.732xVolt
(Phase-Phase)
§ Typically the local utility provides
transformers rated up to 500kVA For maximum connected load
of 99kW,
§ Typically the local utility provides
transformers rated up to 1250kVA For maximum connected load
of 150kW.
§ The diversity they would apply to
apartments is around 60%
§ Maximum HT (11kV) connected load will be
around 4.5MVA per circuit.
§ 4No. earth pits per transformer (2No. for
body and 2No. for neutral earthing),
§ Clearances, approx.1000mm around TC allow
for transformer movement for replacement.
§ Diesel Generator:
§ Diesel Generator Set Produces=3.87 Units
(KWH) in 1 Litter of Diesel.
§ Requirement Area of Diesel Generator
= for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
§ DG less than or equal to 1000kVA must
be in a canopy.
§ DG greater 1000kVA can either be
in a canopy or skid mounted in an acoustically treated room
§ DG noise levels to be less than 75dBA
@ 1meter.
§ DG fuel storage tanks should be a maximum
of 990 Litter per unit Storage tanks above this level will trigger
more stringent explosion protection provision.
§ Current Transformer:
§ Nomenclature of CT:
§ Ratio: input / output current ratio
§ Burden (VA): total burden including
pilot wires. (2.5, 5, 10, 15 and 30VA.)
§ Class: Accuracy required for
operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
§ Accuracy Limit Factor:
§ Nomenclature of CT: Ratio, VA Burden,
Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA
5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
§ As per IEEE Metering CT: 0.3B0.1
rated Metering CT is accurate to 0.3 percent if the connected secondary burden
if impedance does not exceed 0.1 ohms.
§ As per IEEE Relaying (Protection)
CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary
burden is less than 1.0 ohm (100 volts/100A).
|
Quick Electrical Calculation
|
|
|
1HP=0.746KW
|
Star
Connection
|
|
1KW=1.36HP
|
Line Voltage=√3 Phase Voltage
|
|
1Watt=0.846 Kla/Hr
|
Line Current=Phase Current
|
|
1Watt=3.41 BTU/Hr
|
Delta
Connection
|
|
1KWH=3.6 MJ
|
Line Voltage=Phase Voltage
|
|
1Cal=4.186 J
|
Line Current=√3 Phase Current
|
|
1Tone= 3530 BTU
|
|
|
85 Sq.ft Floor Area=1200
BTU
|
|
|
1Kcal=4186 Joule
|
|
|
1KWH=860 Kcal
|
|
|
1Cal=4.183 Joule
|
|